Wiring | 3P3W, 3P4W |
Input | Frequency | 60Hz (50Hz'') |
Voltage | PT: 100/ √3, 110/ √3, 120/ √3, 190/ √3, 100, 110, 120V GPT: 190, 190/ √3 V |
Current | CT: 5A, ZCT: 1.5mA |
Power consumption | Normal: Max. 30W, Operating: Max. 70W |
Control voltage | AC/DC 110/125V (±20%) |
Burden | PT: Max. 0.5VA, Max. 1.0VA |
Output contact | TRIP | Rated | AC 250V 10A / DC 30V 10A, Resistive Load |
Open | AC 2500VA, DC 300W |
ALARM | Rated | AC 250V 5A / DC 30V 5A, Resistive Load |
Open | AC 1250VA, DC 150W |
Insulation Resistance | Over DC 500V 10㏁ |
Dielectric strength | AC 2kV(1kV) / for 1 min |
Output contact2 | TRIP2 | 3 In for 3 hours, 20 In for 2 seconde |
Z1 | 1.15Vn for 3 hours |
Fast Transient Disturbance | Power Input 4kV, Other Input 2kV |
Electrostatic Discharge(ESD) | Air 8kV, Contact 6kV |
Operation temperature | -10℃ ~ 55℃ |
Storage temperature | -25℃ ~ 70℃ |
Humidity | 30% ~ 80% |
Others | Non-impact place, Non-air pollution place |
Weight | 7 kg (HMI: 2kg) |
Standard | IEC 60255-22-1: 1MHz Burst disturbance tests IEC 60255-22-2: Electrostatic discharge tests IEC 60255-22-3: Radiated radio frequency electromagnetic field IEC 60255-22-4: Electrical fast transient/burst immunity test IEC 60255-22-5: Surge immunity test IEC 60255-22-6: Immunity to conducted disturbances induced by radio frequency fields IEC 60255-22-7: Power frequency immunity test IEC 60255-11: Interruptions to and alternating component (ripple) in d.c. auxiliary quantity of measuring relay IEC 60255-25: Electromagnetic emission tests for measuring relays and protection equipment KEMC 1120 |