Question Dear sir, Good day, I have some questions regarding contactor. For example, GMC-9, the rating current for AC-1 is 25A. If I want to connect single phase (240V) load using this contactor, is it that each terminal will able to withstand 25A, or, total of contactor it can withstand is 25A? If it is able to withstand 25 each terminal, can I connect like this (each phase connect with single phase heater load, L1=18A, L2=20A, L3=18A)? Please advice. thank you
Files
Dear Sir,

Regarding to your question, It is OK to use each phase like a L1=18A, L2=20A, L3=18A.

Thank you.
PREV  >> How to Communication between GIMAC - II Plus VS I4XS4UE GIMAC - II Plus: RS845 5-Pins(COM, TX0, TX1...
NEXT  >> Does LS inverter have any solution for winder application?
download of detail page
Category Smart Power Distribution > Low Voltage > Contactor & Overload Relays
Date
Product Meta-MEC Series Contactor & TOR
Question Dear sir, Good day, I have some questions regarding contactor. For example, GMC-9, the rating current for AC-1 is 25A. If I want to connect single phase (240V) load using this contactor, is it that each terminal will able to withstand 25A, or, total of contactor it can withstand is 25A? If it is able to withstand 25 each terminal, can I connect like this (each phase connect with single phase heater load, L1=18A, L2=20A, L3=18A)? Please advice. thank you