Question How to take action when displyed inoperable electrical trip fault in GIS fault indicator?
Files
Inoperable electrical trip fault --> Check the input control circuit wiring(Check Indicator displays "Close" ) Trip Coil disconnection--> Change Coil DC Power / no input Auto Breaker --> Input Auto Breaker Disconnection of wiring--> Repair wiring Auxiliary contact switch contact failure--> Check and exchange auxiliary switch
PREV  >> What are the parallel operation conditions of Cast Resin Transformer?
NEXT  >> How long is the warranty period of SCADA system of LSIS?
download of detail page
Category Smart Power Transmission > Switchgear > HV Switchgear
Date
Product Gas Insulated Switchgear
Question How to take action when displyed inoperable electrical trip fault in GIS fault indicator?
Inoperable electrical trip fault --> Check the input control circuit wiring(Check Indicator displays "Close" ) Trip Coil disconnection--> Change Coil DC Power / no input Auto Breaker --> Input Auto Breaker Disconnection of wiring--> Repair wiring Auxiliary contact switch contact failure--> Check and exchange auxiliary switch