Question How to avoid mechanical resonance frequencies?
Files
Use frequency jump to avoid mechanical resonance frequencies. The inverter will avoid specific
frequency ranges during acceleration and deceleration. Operation frequencies cannot be set
within the preset frequency jump band.
When the operation frequency is increased while the frequency parameter setting value
(voltage, current, RS-485 communication, keypad setting, etc.) is within a jump frequency band,
the frequency will be maintained at the lower limit value of the frequency band. Then, the
frequency will increase when the frequency parameter setting exceeds the range of
frequencies used by the frequency jump band.
PREV  >> I have XMC motion controller. I would like to make specific operating pattern with MC_MOVEABSOLUTE. ...
NEXT  >> I have an issue where the PID operation do not work properly. I have the PID ref. set as 50% and the...
download of detail page
Category Smart Industrial Automation > Low Voltage VFD
Date
Product iS7
Question How to avoid mechanical resonance frequencies?
Use frequency jump to avoid mechanical resonance frequencies. The inverter will avoid specific
frequency ranges during acceleration and deceleration. Operation frequencies cannot be set
within the preset frequency jump band.
When the operation frequency is increased while the frequency parameter setting value
(voltage, current, RS-485 communication, keypad setting, etc.) is within a jump frequency band,
the frequency will be maintained at the lower limit value of the frequency band. Then, the
frequency will increase when the frequency parameter setting exceeds the range of
frequencies used by the frequency jump band.
ListList