Category Smart Power Distribution > Low Voltage > EMPR Date
Question EMPR relay configuration reg
Files
Dear sir,
Wheather in EMPR 97-98,95-96,07-08 outputs are configurable? if possible kindly send the details. our problem is when we are switch on the feeder the O/l is NC.the trip lamp is glowing.how to rectify?
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Dear Mr. Jeganathan.
EMPR's outputs are fixed contacts
When ordering the EMPR, you must select the contact's spec.
1) DMP-S/T(a) Type : 2a1b
2) DMP-SZ/TZ(a) Type : 2a .or. 2a1b .or. 2b
3) DMP-SI/TI Type : 2a1b

Great thanks.
PREV  >> Failure of VFD SV110iP5A-4NE
NEXT  >> EMPR relay configuration reg