Category Smart Industrial Automation > HMI > XGT Panel Date
Question XP10 'System Memory' connect to G7M
Files
Dear Sir

I have a project with XP10BKB and G7M-DR60A ,

I wanted to count in LONG format Data
For sending or Receiveing data from XP10 in ' Numeric Tag property' to PLC,
I myself used 'System Memory' in 'Common Resource',Block Communication,
and then 'ADD' some of %MW in PLC and system memory for XP10 in 'Direction' of PLC->HMI,
I sent data to PLC but i cannot recieve data from HMI<-PLC in my Numeric Tag with
system memory address of XGT.
I am looking forward hearing from you.

Thank you in advancs.

Mrs Mokhtar
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Dear sir,

I'm sorry for late reply.
If you want to read and write LONG format data of '%MW' area in PLC,
you insert the Numeric Tag which the items of 'Write Enabled' and 'Long' type are checked .
You don't need other settings.
If possible, please send your project file.

Regards,
Namyong Kim
NEXT  >> OPC server for XGK CPU
download of detail page
Category Smart Industrial Automation > HMI > XGT Panel
Date
Question XP10 'System Memory' connect to G7M
Dear Sir

I have a project with XP10BKB and G7M-DR60A ,

I wanted to count in LONG format Data
For sending or Receiveing data from XP10 in ' Numeric Tag property' to PLC,
I myself used 'System Memory' in 'Common Resource',Block Communication,
and then 'ADD' some of %MW in PLC and system memory for XP10 in 'Direction' of PLC->HMI,
I sent data to PLC but i cannot recieve data from HMI<-PLC in my Numeric Tag with
system memory address of XGT.
I am looking forward hearing from you.

Thank you in advancs.

Mrs Mokhtar
------------------------------------------------------------------
Dear sir,

I'm sorry for late reply.
If you want to read and write LONG format data of '%MW' area in PLC,
you insert the Numeric Tag which the items of 'Write Enabled' and 'Long' type are checked .
You don't need other settings.
If possible, please send your project file.

Regards,
Namyong Kim