• buy now
  • contact us
  • downloads
  • faq
  • news
  • about
  • Variable Frequency Drives
  • Contactors & Relays
  • Manual Motor Starters
  • LV Circuit Breakers
  • Vacuum Circuit Breaker
  • Panel Solutions
  • Energy Storage Solutions
Home > Manual Motor Starters > Meta-MEC MMS

Overview

Meta-MEC MMS

Manual Motor Starters Efficiency through various functions and compact design. Complete ranges up to 100A and 100kA Wide variety of accessories

  • Features
  • Characteristics
  • Ratings
Features

Characteristics
General
Meta-MEC MMSs are suitable for switching and protecting three-phase induction motors of up to 45kW at 400VAC and for loads with rated currents of up to 100A.
 
Types
- MMS32S, MMS32H, MMS63S, MMS63H, MMS100S, MMS100H
Rating
- It covers all ratings up to 100A


Function
  • Protection of group installation
  • Protection of circuits
  • Motor protection & Starter protection
  • Wide range of ambient temperature compensation
  • Phase failure protection
Standard
  • The components fulfill the international standard IEC 60947.
  • In U.S, the devices can be used as Manual Motor Starter in Group Installations according UL508. The approval for UL508 Type E Combination Starter is under preparation.

Design concept for user’s efficiency
  • Dial cover for current setting, cover lock device, large scale letter
  • Identification label
  • Handle lock function in OFF position & Three position handle
  • Trip test device
  • Insulation barrier


Mounting & Connection
  • Terminals
  • 35mm/75mm din-rail standard mounting & screw mounting
  • Finger safe terminal cover
  • Direct adapter (Connection kit with mini Magnetic Contactor)


 
Accessories
  • Front mounting auxiliary switch
  • Side mounting auxiliary switch
  • Side mounting alarm switch
  • Side mounting shunt release
  • Side mounting undervoltage release
  • Side mounting undervoltage release with 2NO switch)

Ratings
Function - Motor protection (Trip class 10 and 20)
  • Short circuit
  • Over-current
  • Phase failure
  • Adjustable thermal release
  • Ambient temperature compensation

Ratings
  • Ampere Frame : 32, 63, 100AF
  • Rated operating voltage (Ue) : 1000V (690V for MMS-32)
  • Rated frequency (Hz) : 50/60Hz
  • Rated insulation voltage (Uimp) : 8kV (6kV for MMS-32)
  • Utilization category : Cat A., AC3
  • Instantaneous short circuit : 13 x Ie max
  • Wide operation temperature : -20 ~ +60℃